CALOGTW2-ISO

Quantity:  
2-Wire universal transmitter (DIN mount, loop powered, isolated)

This versatile 2-wire transmitter accepts a wide range of standard input types, and outputs 4-20mA. USB programming is hassle free – it takes just 2 minutes using our purpose-built software, and no calibration or power supply is required.

  • 2-wire universal transmitter (DIN-mount, isolated)
  • Accepts current, voltage, thermocouple, RTD and potentiometer input
  • Loop powered, 4-20mA output
  • LED indicator for error notification
  • USB port for PC programming (requires Bridge Key)
  • Potentiometer for fine offset adjustment of current output

General

Configuration 2-wire 4-20mA (loop powered)
Housing 35mm DIN mount case: 79 x 20 x 68mm (H x W x D)
Operating humidity 5-85%RH max (non-condensing)
Operating temperature -20 to +85°C
Power supply 10.5-36V DC
Status LED Flashing=Normal, On=Fault
Storage temperature -20 to +100°C
USB programmable Configure using simple TM Setup software. Requries Bridge Key (sold separately)

Operation

Accurate to <±0.03% FSO typical
Ambient drift <±0.003%/°C FSO typical
EMC Compliance EN61326 (Emissions); EN61326 (Immunity); EN61010-1 (Safety)
Isolation test voltages between input and output 3750Vac for 1min
Max output current Limited to <28mA (emission and immunity)
Noise immunity 125dB CMRR average (2.0kVdc limit)
Output load resistance 650O at 24V DC (50O/V above 10.5V DC)
Potentiometer For fine offset adjustment of current output
R.F. immunity <1% effect FSO typical
Response time 400msec typical(10-90% 300msec typical)
Supply voltage sensitivity <±0.005%/V FSO

Voltage Input Specifications

Input resistance 300kO min
Linearity & repeatability <±0.02% FSO typical
Max over-range 60Vdc continuous
USB programmable span 100mV to +/-10Vdc (bipolar)
USB programmable zero 0-±99% of the span

Current Input Specifications

Field programmable span 1µA-24mAdc
Input resistance 10O
Linearity & repeatability <±0.02% FSO typical
Max over-range 50mAdc continuous
USB programmable zero 0-±99% of the span

Thermocouple Input Specifications

Accuracy E, J, K, N, T: <±1°C, B, R, S: <±2°C
CJC error <±1°C
Cold junction comp. -20 to +90°C
Field programmable span Refer to ordering information for min/max ranges for each type
Input impedance 1MO min
Sensor break output drive Function high upscale / function low downscale
T/C lead resistance 100O max
Temperature drift E, J, K, N, T: <±0.05°C, B, R, S: <±0.2°C
Thermocouple types B, E, J, K, L, N, R, S, T
USB programmable zero 0-±99% of the span

RTD Input Specifications

Available RTD types JIS, Pt100/1000, Pt392, Cu10
Lead wire resistance Pt100: 10O/wire max, Pt1000: 5O/wire max (0.02% FSO offset error per O of lead resistance)
Linearity (Pt100) 0.02% FSO for span inputs =200°C; 0.1% FSO for span inputs =850°C
Linearity (Pt1000) 0.02% FSO for span inputs =200°C; 0.2% FSO for span inputs =520°C
RTD input Pt100 or Pt1000 DIN 3-wire type
Sensor break output drive Function high upscale / function low downscale
Sensor current 0.15mA nominal
USB programmable span -200 to +850°C
USB programmable zero 0-±99% of the span

Potentiometer Input Specifications

Excitation voltage 1.2Vdc
Field programmable span 0.1-100%
Field programmable zero 0-90% of the span
Linearity and repeatability <±0.02% FSO typical
Potentiometer input 3-wire potentiometer
Potentiometer resistance 0-2KO low pot, 0-1MO high pot

Included Accessories: Datasheet, mounting clips


My Cart
Item added to cart
Item copied to cart